2 ZONE FIRE ALARM PANEL ANG1F02C
- Microprocessor based with LCD back lit type.
- All zonal status at LCD and LED.
- Energy Saving Design for more battery life.
- As per IS2189:1999 Fire alarm code of practice.
- Modular Construction.
- Clear labelled all indicating lamp, control switch and user instruction based sticker on Front.
- Soft Touch programmable Function & Control switch.
- Monitor for Mains On, Batt. On, System ON, Charger ON, Fire, Silence, Earth, Battery Low.
- Control Switch: Lamp Test, Evacuate, Silence (Fire/Fault/Power Fault) and Reset.
- Zone display: Fire, Open, Short and Isolate.
- Potential Free relay control for signal transfer to remote area.
- 12VDC auxiliary supply for auto dialler.
- 24VDC auxiliary supply for other devices.
- When mains fails auto change over to battery vice-versa.
- PWM based built in charger with auto cut off.
- In built auto charger and battery housing for 7 Ah x 12V -2 No.
- System ON/OFF switches with protective fuse for AC/DC/Battery.
- Fabrication MS with powder coated, Top entry cable entry, front operable door.
Technical Specifications:
| ELECTRICAL | |
| Power Supply, AC Input Supply DC Input Supply | 230 V AC, 50Hz 24 V DC |
| Operating Conditions | -10 to 45 C, 95% RH Max. |
| Operating Voltage | 24 V DC |
| Normal Loop Voltage | 20.7 DC |
| Open Threshold Current | 4.2 mA |
| Short Circuit Threshold Current | 40 mA |
| Stand by Threshold Current | 8.2 mA |
| Alarm Current | 20 - 35 mA |
| Quiescent Current | 50mA Plus 4.2mA per Zone |
| Colour of the Panel | White |
| ALARM OUTPUT , Standard Common Output | 0.2A per Zone. |
| REMOTE INDICATION OUTPUTS, Outputs | Fire Relay Contacts (230V 2A Contact). |