A sharper eye for a safer world.

Control Panel

24 ZONE FIRE ALARM PANEL ANG1F24C

  • Microprocessor based with LCD back lit type.
  • All zonal status at LCD and LED.
  • Energy Saving Design for more battery life.
  • As per IS2189:1999 Fire alarm code of practice.
  • Modular Construction.
  • Clear labelled all indicating lamp, control switch and user instruction based sticker on Front.
  • Soft Touch programmable Function & Control switch.
  • Monitor for Mains On, Batt. On, System ON, Charger ON, Fire, Silence, Earth, Battery Low.
  • Control Switch: Lamp Test, Evacuate, Silence (Fire/Fault/Power Fault) and Reset.
  • Zone display: Fire, Open, Short and Isolate.
  • Potential Free relay control for signal transfer to remote area.
  • 12VDC auxiliary supply for auto dialler.
  • 24VDC auxiliary supply for other devices.
  • When mains fails auto change over to battery vice-versa.
  • PWM based built in charger with auto cut off.
  • In built auto charger and battery housing for 7 Ah x 12V -2 No.
  • System ON/OFF switches with protective fuse for AC/DC/Battery.
  • Fabrication MS with powder coated, Top entry cable entry, front operable door.

Technical Specifications:

ELECTRICAL 
Power Supply, AC Input Supply DC Input Supply230 V AC, 50Hz 24 V DC
Operating Conditions-10 to 45 C, 95% RH Max.
Operating Voltage24 V DC
Normal Loop Voltage20.7 DC
Open Threshold Current4.2 mA
Short Circuit Threshold Current40 mA
Stand by Threshold Current8.2 mA
Alarm Current20 - 35 mA
Quiescent Current50mA Plus 4.2mA per Zone
Colour of the PanelWhite
ALARM OUTPUT , Standard Common Output0.2A per Zone.
REMOTE INDICATION OUTPUTS, Outputs Fire Relay Contacts (230V 2A Contact).